Technical data | KL3041 | KS3041 |
---|
Number of inputs | 1 |
Power supply | 24 V DC via power contacts |
Signal current | 0…20 mA |
Technology | single-ended |
Internal resistance | 80 Ω + 0.7 V |
Common-mode voltage UCM | – |
Conversion time | ~ 1 ms |
Resolution | 12 bit |
Measuring error | < ±0.3="" %="" (relative="" to="" full="" scale=""> |
Surge voltage resistance | 35 V max. |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | only load |
Current consumption K-bus | typ. 65 mA |
Bit width in the process image | input: 1 x 16 bit data (1 x 8 bit control/status optional) |
Configuration | no address or configuration setting |
Special features | with sensor supply |
Weight | approx. 70 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals | CE, UL, Ex, GL |