General specifications | |
---|---|
Signal type | Analog output |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Ripple | ? 10 % |
Rated current | ? 35 mA |
Power dissipation | ? 600 mW |
Power consumption | ? 700 mW |
Input | |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-) |
Input signal | 4 ... 20 mA , limited to approx. 27 mA |
Input voltage | depending on switch configuration open loop voltage of the control system < 19 V open loop voltage of the control system < 26 V |
Voltage drop | depending on switch configuration open loop voltage of the control system < 19 V: approx. 5 V at 20 mA open loop voltage of the control system < 26 V: approx. 12 V at 20 mA |
Input resistance | > 100 k?, with field wiring open |
Output | |
Connection side | field side |
Connection | SL2: 5a(+), 5b(-) |
Current | 4 ... 20 mA |
Load | 0 ... 625 ? |
Voltage | ? 12.5 V at 20 mA |
Ripple | 20 mV rms |
Transfer characteristics | |
Deviation | at 20 °C (68 °F), 4 ... 20 mA ? ± 0.1 % incl. non-linearity and hysteresis |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) |
Rise time | 10 to 90 % ? 100 ms |
Indicators/settings | |
Display elements | LED |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21:2012 For further information see system description. |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting | on Termination Board |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | CESI 11 ATEX 012 |
Certificate | PF 11 CERT 1845 X |
Directive conformity | |
International approvals | |
UL approval | |
IECEx approval | IECEx CES 11.0010 |