General specifications | |
---|---|
Signal type | Digital Output |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 3 |
Performance level (PL) | PL e |
Supply | |
Connection | loop powered |
Rated voltage | 19 ... 30 V DC loop powered |
Power dissipation | < 1.3 W |
Power consumption | < 1.3 W |
Input | |
Connection side | control side |
Connection | Input SL1: 8a(+), 7a(-) ; test input SL1: 3a(-), 3b(+), 4a(+), 4b(+) |
Pulse/Pause ratio | 150 ms / 150 ms |
Test pulse length | max. 4 ms from DO card |
Test input | see Functional Safety Manual |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 27.6 V |
Rated voltage | 19 ... 27.6 V loop powered |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ? 36 mA (minimum load current DO card) |
Output | |
Connection side | field side |
Connection | SL2: 5a, 7a; 1a, 3a |
Contact loading | 253 V AC/2 A/cos ? 0,7; 30 V DC/2 A resistive load |
Minimum switch current | 10 mA / 24 V DC |
Energized/De-energized delay | 150 ms / 150 ms |
Mechanical life | 2 x 107 switching cycles |
Fuse rating | 3.15 A |
Transfer characteristics | |
Switching frequency | < 3 Hz |
Galvanic isolation | |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff |
Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff |
Indicators/settings | |
Display elements | LEDs |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Low voltage | |
Machinery Directive | |
Conformity | |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2013 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
Mechanical specifications | |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting | on Termination Board |
Coding | no pin trimmed For further information see system description. |
Data for application in connection with hazardous areas | |
Certificate | PF 17 CERT 4312 X |
Directive conformity |