General specifications | |
---|---|
Signal type | Digital Input |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | terminals 14, 15 |
Rated voltage | Или отправьте нам запрос на Hz |
Power dissipation | 1 W |
Power consumption | max. 1.5 W |
Input | |
Connection side | field side |
Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values | acc. to EN60947-5-6 (NAMUR), see system description for electrical data |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ? 0.1 mA , short-circuit I > 6 mA |
Output | |
Connection side | control side |
Connection | output I: terminals 7, 8 ; output II: terminals 8, 9 |
Switching voltage | max. 40 V |
Switching current | max. 100 mA , short-circuit protected |
Signal level | 1-signal: switchИли отправьте нам запрос на 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current ? 10 µA) |
Output I, II | signal ; electronic output, passive |
Transfer characteristics | |
Switching frequency | ? 5 kHz |
Galvanic isolation | |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/Output | not available |
Indicators/settings | |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Low voltage | |
Conformity | |
Electromagnetic compatibility | NE 21:2012 |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | PTB 98 ATEX 2164 |
Supply | |
Output | |
Galvanic isolation | |